MELODY2TM Cassettes aiRthRowinmetRes( ) Louvres all open MELODY2TM High speed Medium speed Low speed 61 3.8 3.2 2.7 62 4.0 3.4 2.8 63 4.8 4.1 3.4 92 3.0 2.6 2.1 93 3.4 2.9 2.4 94 4.3 3.7 3.0 Notes: 1. The deflectors were adjusted to use the Coanda effect to obtain an air flow pattern that adheres as closely as possible and parallel to the ceiling. 2. The air throw is defined as the distance at which the air flow speed falls to 0.2 m/s, when the air flow leaves the unit parallel to the ceiling. 3. The values are to be considered as indicative, as they may vary according to the type of ceiling, room dimensions and even the furniture used. opeRatingLimits Maximum water-side pressure: Minimum inlet water temperature: 5 °C Water circuit 1400 kPa (142 mWG) Maximum inlet water temperature: 80 °C Minimum temperature: 5 °C Indoor temperature Maximum temperature: 32 °C for units with electric heaters 230 V - 50/60 Hz single-phase Power supply Nominal operating limits Min. 207 - Max 253 V for units without electric heaters Min. 216 - Max 244 V for units with electric heaters 58 58 CATALOGUE 2021