AQUACIATTMLD ILD Water chillers Heat pump teChniCalChaRaCteRistiCs- Coolingonly AQUACIATTM LD 0150R 0180R 0200R 0202R 0240R 0260R Cooling Standard unit Nominal capacity kW 41,8 47,3 52,9 56,1 63,6 71,2 Full load performances* CA1 EER kW/kW 2,95 2,94 2,93 2,97 2,89 2,90 Nominal capacity kW 54,6 62,7 69,4 74,3 84,6 93,0 CA2 EER kW/kW 3,60 3,61 3,51 3,61 3,63 3,49 SEER 12/7°C Comfort low temp. kWh/kWh 4,41 4,48 4,50 4,62 4,41 4,31 Ƞs cool 12/7°C % 173 176 177 182 174 169 Seasonal energy efficiency** SEER 23/18°CComfort medium temp.kWh/kWh 5,74 5,76 5,71 5,83 5,38 5,41 SEPR 12/7°CProcess high temp. kWh/kWh 6,30 6,23 6,23 6,21 5,92 5,46 SEPR 2/-8°C Process medium temp. kWh/kWh 3,56 3,64 3,76 3,87 3,64 3,60 - Part Load integrated values IPLV.SI kW/kW 4,972 5,047 5,216 5,298 5,369 4,630 Sound levels Standard unit and High outdoor temperature option Sound power(1) dB(A) 81,5 82,0 83,5 83,5 89,0 89,0 Soundpressure at 10 m(2) dB(A) 50,0 50,5 52,0 52,0 57,5 57,5 Unit + Xtra Low Noise option Sound power(1 ) dB(A) 78,5 79,0 80,0 80,0 80,0 80,0 Sound pressure at 10 m(2) dB(A) 47,0 47,5 48,5 48,5 48,5 48,5 Dimensions Length mm 1061 1061 1061 1061 1061 1061 Width mm 2050 2050 2050 2050 2050 2050 Height mm 1330 1330 1330 1330 1330 1330 Unit height (XtraFan option) mm 1341 1341 1341 1341 1341 1341 Unit height (optional buffer tank) mm 1930 1930 1930 1930 1930 1930 Unit height (XtraFan + buffer tank option) mm 1972 1972 1972 1972 1972 1972 Operating weight with micro-channel coils(3) Standard unit kg 404 405 424 424 430 439 Unit + High-pressure single-pump option kg 425 426 444 444 450 460 Unit + High-pressure dual-pump option kg 451 453 471 471 477 487 Unit + high-pressure single-pump and buffer tank options kg 776 778 796 796 802 812 Unit + high-pressure dual-pump and buffer tank options kg 803 805 823 823 829 838 * In accordance with standard EN14511-3:2018. ** In accordance with standard EN14825:2013, average climate CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 12 °C/7 °C, outdoor air temperature 35 °C, evaporator fouling factor 0 m2. k/W CA2 Cooling mode conditions: evaporator water inlet/outlet temperature 23 °C/18 °C, outdoor air temperature 35 °C, evaporator fouling factor 0 m2. k/W Ƞs cool12/7°C & SEER 12/7°CValues in bold comply with Ecodesign Regulation (EU) No. 2016/2281 for Comfort applications SEER 23/18 °C Values in bold comply with Ecodesign Regulation (EU) No. 2016/2281 for Comfort applications SEPR-2/-8 °C Values in bold comply with Applicable Ecodesign regulation: EU) No 2015/1095 for Process applications( IPLV.SI Calculated as per standard AHRI 551-591 (1) IndB ref=10-12W, (A) weighting. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). Measured in accordance with ISO 9614-1. (2) In dB ref 20 µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). For information, calculated from the sound power level Lw(A). (3) Values are guidelines only. Refer to the unit name plate. Eurovent certified values 348 348 CATALOGUE 2021