AQUACIAT TMLD ILD Water chillers Heat pump teChniCalChaRaCteRistiCs- ReveRsibleheatpUmp AQUACIATTM ILD 150 180 200 240 260 300 302 360 390 450 520 600 Heating Standard unit HA1 Nominal capacity kW 42.3 46,4 53,2 61,2 68,0 77,6 81,7 92,2 100 116 135 155 Full load performances* COP kW/kW 3,69 3,69 3,76 3,72 3,64 3,46 3,78 3,80 3,76 3,68 3,61 3,47 HA2COPNominal capacity kW 41,5 46,3 51,7 59,3 65,9 75,0 78,9 89,5 97,4 112 130 150 kW/kW 3,05 3,02 3,01 3,01 2,98 2,85 3,11 3,05 3,06 3,00 2,94 2,86 Standard unit SCOP30/35°C kW/kW3,323,393,533,403,403,283,51 3,503,573,543,443,42 Seasonal energy efficiency** ηs heat30/35°C % 130133138133133128137137140139135134 HA1 Prated kW 35,5 31,6 36,3 43,8 50,1 55,7 56,8 81,5 72,3 84,2 99,4 111 Energy labelling A+ A+ A+ A+ A+ A+ A+ -- -- - Cooling Standard unit CA1 Nominal capacity kW 37,7 43,1 49,4 58,0 63,1 70,2 77,0 84,9 95,1 112,4130,5148,2 Full load performances* EER kW/kW 2,80 2,66 2,61 2,72 2,66 2,43 2,75 2,66 2,66 2,65 2,73 2,54 CA2EERNominal capacity kW 47,1 53,9 62,7 70,7 78,2 88,5 96,5 106,9116,6141,9161,6185,2 kW/kW 3,23 3,11 3,04 3,08 3,04 2,81 3,14 3,09 3,05 3,05 3,12 2,88 Standard unit SEER 12/7°C Comfort low temp. kWh/kWh3,64 3,67 3,70 3,53 3,49 3,37 3,83 3,70 3,76 4,00 3,65 3,62 Seasonal energy efficiency** SEPR 12/7°CProcess high temp. kWh/kWh4,92 4,95 4,74 4,53 4,44 4,72 5,16 4,67 4,62 5,15 4,59 4,95 Unit with low-temperature SEPR Process medium brine solution option -2/-8°C kWh/kWh2,58 2,58 2,61 2,96 2,98 2,86 2,70 2,86 3,04 2,94 2,80 2,68 Seasonal energy efficiency** temp. Part Load integrated values IPLV.SI kW/kW4,4644,4474,4094,1274,1024,0334,4754,3144,3784,7954,2464,295 Sound levels Standard unit Sound power(1) dB(A) 80 81 81 86 87 87 84 84 84 84 90 90 Sound pressure at10 m(2) dB(A) 49 49 49 55 55 55 52 52 52 52 58 58 Unit + Xtra Low Noise option Sound power(1) dB(A) 79 80 80 80 80 80 83 83 83 83 83 83 Sound pressureat 10 m(2) dB(A) 48 48 48 48 48 48 51 51 51 51 51 51 Dimensions Length mm 109010901090109010901090227022702270227022702270 Width mm 210921092109210921092109212321232123212321232123 Height mm 133013301330133013301330133013301330133013301330 Height withBuffer TankModule mm 193019301930193019301930193019301930193019301930 Operating weight(3) Standard unit kg 497 506 543 549 559 564 777 896 905 979 10531057 Unit + High pressure single pump option kg 539 548 585 591 601 606 844 963 972 1050 1127 1131 Unit + High pressure dual pump option kg 565 574 611 617 627 632 889 10081017 10981164 1168 Unit + high pressure single pump + Water buffer tank module option kg 935 943 981 986 996 1001 1276 13951404148215601563 Unit + high pressure dual-pump + Water buffer tank module option kg 961 969 10061012 102210271321 144014491531 15971600 * In accordance with standard EN14511-3:2013. ** In accordance with standard EN14825:2016, average climate conditions. HA1 Conditions in heating mode: water type heat exchanger water outlet/inlet temperature 30 °C/35 °C, outside air temperature tdb/twb = 7 °C db/6 °C wb, evaporatorfouling factor 0 m. k/W2 HA2 Conditions in heating mode: water type heat exchanger water outlet/inlet temperature 40 °C/45 °C, outside air temperature tdb/twb = 7 °C db/6 °C wb, evaporatorfouling factor 0 m. k/W2 CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 12 °C/7 °C, outdoor air temperature 35 °C, evaporator fouling factor 0m. k/W2 CA2 Cooling mode conditions: evaporator water inlet/outlet temperature 23 °C/18 °C, outdoor air temperature 35 °C, evaporator fouling factor0 m. k/W2 ŋs heat 30/35°C& SCOP 30/35°CValues in bold comply with Ecodesign Regulation (EU) No. 813/2013 foheating applicationr SEER 12/7°C& SEPR 12/7°C Values calculated according to EN14825:2016 SEPR -2/-8°C Values calculated according to EN14825:2016 IPLV.SI Calculated as per AHRI standard 551-591 (SI). (1) indB ref=10-12 W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with ISO 9614-1 and certified by EUROVENT (2) In dB ref 20 µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Value calculated from the sound power level Lw(A). (3) Weights given as a guide. Refer to the unit name plate. Eurovent certified values 364 364 CATALOGUE 2021