SC Air-cooled condensing units Technical characteristics SC 240 320 360 420 485 540 600 Cooling capacity (1) (kW) 55,5 70,0 86,4 103,6 115,5 124,6 138,4 Cooling Power input (3) (kW) 16,8 24,8 24,4 28,0 32,9 39,1 44,9 capacities Energy efficiency rating (EER) 3,31 2,82 3,55 3,70 3,51 3,19 3,08 Heating capacity (2) (kW) 64,9 81,8 94,2 108,9 123,5 134,3 148,2 Heating Power input (3) (kW) 15,6 20,9 23,0 28,8 30,9 36,8 38,8 capacities Coefficient of performance (COP) 4,15 3,91 4,10 3,79 4,00 3,65 3,82 Nominal air flow (m3/h) 20.000 39.000 37.000 Available static pressure (mm.w.c) -- Outdoor circuit Quantity 1 2 axial fan Diameter (mm) 800 Power (kW) 2,0 / 1,3 Speed (r.p.m.) 895 / 705 Type Scroll No. compressors/circuits/stages 2 / 2 / 2 Compressor Oil type Copeland 3MAF 32 cST, Danfoss POE 160 SZ, ICI Emkarate RL32 CF, Mobil EAL Artic 22 CC Volume of oil (l) 2 x 3.3 2 x 3.3 2 x 6.2 2 x 6.2 2 x 6.2 2 x 6.2 2 x 6.2 Circuit 1: Liquid line 5/8” 5/8” 5/8” 5/8” 5/8” 7/8” 7/8” Refrigerant Circuit 1: Gas line 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” connections Circuit 2: Liquid line 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” 7/8” Circuit 2: Gas line 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” Type R-410A Global Warming Potential (GWP) (4) 1.720 Refrigerant Load up to 7,5 m (kg) 17,4 22,2 22,7 31,4 31,4 33,4 33,6 Environment impact (tCO e)2 36,3 46,4 47,4 65,6 65,6 69,7 70,2 Mains voltage 400 V / III ph / 50 Hz (±10%) Electrical features Electric power supply 3 wires + GND Compressor(s) (A) 40,2 50,2 58,2 68,9 79,6 91,1 102,6 Maximum Fan (A) 4,3 4,3 8,6 8,6 8,6 8,6 8,6 absorbed current Control (A) 1,8 1,8 1,8 1,8 1,8 1,8 1,8 Total (A) 46,3 56,3 68,6 79,3 90,0 101,5 113,0 Length (mm) 1.811 1.811 2.201 Dimensions Width (mm) 1.066 1.066 2.069 Height (mm) 1.763 2.063 1.966 Weight (kg) 492 544 974 1.024 1.029 1.078 1.127 (1) Rated conditions: Evaporation temperature = 5 °C, outdoor operating temperature = 35 °C, overheating = 5 °C (2) Rated conditions: Condensing temperature = 49 °C, outdoor operating temperature = 7 °C, overheating = 0 °C (3) Total input power by compressors and fan motor assemblies under these conditions. (4) Global Warming Potential of one kilogram of fluorinated greenhouse gas relative to one kilogram of carbon dioxide over a period of 100 years. 284 284 CATALOGUE 2021