AQUACIATPOWER TM LD Water chillers teChniCalChaRaCteRistiCs AQUACIATPOWER TMLD ST 602 650 750 800 1000 1100 1250 1350 1500 Cooling Standard unit Nominal capacity kW 168 181 198 216 261 300 331 365 397 Full load performances* CA1 EER kW/kW 3,04 3,12 2,98 2,97 2,90 2,97 2,92 2,95 2,90 Nominal capacity kW 216 247 263 297 336 393 428 475 510 CA2 EER kW/kW 3,6 3,89 3,59 3,7 3,37 3,53 3,4 3,47 3,37 Standard unit kWh/kWh 4,15 4,18 4,10 4,09 4,10 4,15 4,19 4,21 4,16 Seasonal energy efficiency** % 163 164 161 161 161 163 165 165 163 kWh/kWh 4,77 4,71 4,29 4,76 4,33 4,56 4,46 4,67 4,50 Unit with low temperature kWh/ brine option 2,81 3,08 3,14 2,99 3,13 3,05 3,04 2,76 3,23 Seasonal energy efficiency ** kWh Part Load integrated values IPLV.SI kW/kW 4,566 4,570 4,538 4,508 4,500 4,610 4,612 4,690 4,579 Sound levels Standard unit Soundpower(1) dB(A) 91 92 92 92 92 93 93 93 93 Sound pressure at10 m(2) dB(A) 59 60 60 60 60 60 60 61 61 Unit + Low Noise option Sound power(1) dB(A) 89 90 90 90 90 91 91 92 92 Sound pressureat 10 m(2) dB(A) 57 58 58 58 58 59 59 60 60 Unit + Xtra Low Noise option Soundpower(1) dB(A) 84 84 84 85 85 86 86 86 86 Sound pressure at10 m(2) dB(A) 52 52 52 53 53 54 54 54 54 Dimensions - Standard unit Length mm 2410 3604 Width mm 2253 2253 Height mm 2324 2324 Unit + Buffer tank module option mm 3604 4798 Operatingweight(3) Standard unit kg 1222 1265 1266 1395 1416 1875 1911 2080 2137 Unit + Low Noise option kg 1305 1348 1349 1503 1524 2001 2037 2224 2281 Unit + Low Noise option + HP dual-pump hydraulic module kg 1483 1526 1527 1681 1717 2197 2278 2465 2521 Unit + Low Noise option + HP dual-pump hydraulic module + water buffer tank kg 2442 2485 2486 2640 2676 3156 3237 3424 3480 module Compressors Hermetic Scroll 48.3 r/s Circuit A 1 1 1 2 2 2 2 3 3 Circuit B 2 2 2 2 2 3 3 3 3 No. of power stages 3 3 3 4 4 5 5 6 6 Refrigerant(3) R410A (GWP = 2088 following ARI4) * In accordance with standard EN14511-3:2013. ** In accordance with standard EN14825:2016, average climate conditions. *** 30 % brine solution CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 12 °C/7 °C, outdoor air temperature 35 °C, evaporator fouling factor0 m. k/W2 CA2 Cooling mode conditions: evaporator water inlet/outlet temperature 23 °C/18 °C, outdoor air temperature 35 °C, evaporator fouling factor0 m. k/W2 Ƞs cool 12/7& SEER°C 12/7 °CValues in bold complywith Ecodesign Regulation (EU) No. 2016/2281 for Comfort application SEPR 12/7°C Values calculated according to EN14825:2016 SEPR -2/-8°C Values in bold comply with Ecodesign Regulation (EU) No. 2015/1095 for Process application NA Not authorised for the specific application for the EEC market IPLV.SI Calculated as per AHRI standard 551-591 (SI). (1) indB ref=10-(12) W, 'A' weighted. Declared dual number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3 dB(A). Measured in accordance with ISO 9614-1 and certified by Eurovent. (2) I n dB ref 20µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information, calculated from the sound power Lw(A). (3) Values are guidelines only. Refer to the unit name plate. Eurovent certified values 424 424 CATALOGUE 2021