FLOWAYCLASSIC® Air handling unit Description Casing Electric heaters ■ Double-skin panels made from steel sheet metal, galvanised ■ High-limit safety thermostats with automatic and manual on both sides, thickness 0.8 mm. reset. ■ External panels made from galvanised steel, precoated in ■ 2- or 3-stage control based on the selected option, controlled RAL7035. by theFLOWAY Control.® ■ M0/A1 insulation fire rating. DX coil ■ Mineral wool, thickness 50mm. ■ Copper tubes, aluminium fins. Filtration ■ For reversible heating/cooling operation. ■ M5, F7, F9 filters. ■ Internal space optimised for VRV units. ■ Filter cells kept compressed by a special system to ensure ■ Condensate drain pan in stainless steel. a leaktight seal. List of outdoor units optimised for FLOWAY Access available® ■ Classic PHE & RHE-RHEZ, Vertical PHE models: fouling on request. value monitored by analogue sensor and displayed byElectrics box controller. ■ Electrics box for power, control and regulation built into the ■ Access RHE model: pressure switch control on each air flow. unit, comprising as standard: Pressure switch status displayed by controller. - Power supply (3-Ph/400 V/Earth or 1-Ph/230 V/Earth). Ventilation - Main disconnect switch. ■ "Plug Fan" type direct-drive fan. - Protected transformer. ■ Plug fan driven by an electronically commutated motor with - Protection and control of all electrical components by a built-in speed control. circuit breaker. Heat recovery units - Peripheral options and power terminal block. ■ "Contra Flow" plate heat exchanger equipped with a - Factory-programmed PLC control. motorised bypass (Vertical PHE and Classic PHE models). - Hand-held cabled micro-terminal. Efficiency greater than 80% across the range of air flows. - Fault summary contact. ■ Rotary heat exchanger equipped with rotation speed control - 3 temperature sensors. (Classic RHE model). - 4 pressure sensors (2 pressure sensors and 2 pressure Efficiency greater than 80% at nominal flow rate. switches on the Access model). ■Purge sector as standard (Classic RHEZ model) Accessories ■ Constant speed rotary heat exchanger (Access RHE model). Damper formed of airfoil blades, powered by a TOR servomotor 80% efficiency at nominal flow rate. with spring return. Hydraulic coil Flexible sleeve. ■ Copper pipes, aluminium fins. Adjustable feet. ■ Coil can be integrated or additional (cased). CO2 air quality sensor. ■ With the accessories fitted: 2- or 3-way control valve and Roof. 0-10 V actuator controlled byFLOWAY Control for precise® Canopy. setpoint maintenance. Mixing section (Classic RHE model). ■ Stainless steel condensate drain pan (cooling coil or mixed coil only). Power supply FLOWAY®CLASSIC PHE and CLASSIC RHE-RHEZ Size Nominal flow rate (m³/h) Rated current (A) Supply type 1000 1000 5,8 1/home/webapps/asp_fr/data/asp/publications/mc-graphics/publications/ciat/catalogue-ciat-2021---product-and-system-solutions230 V - 50 Hz 2000 2000 4,2 3000 3000 7,0 4000 4000 8,6 5000 5000 8,6 3/home/webapps/asp_fr/data/asp/publications/mc-graphics/publications/ciat/catalogue-ciat-2021---product-and-system-solutions400 V - 50 Hz 6000 6000 10,0 7500 7500 10,0 10000 10000 19,0 15000 15000 24,6 FLOWAY®ACCESS RHE Size Nominal flow rate (m³/h) Rated current (A) Supply type 1000 1000 5,4 1/home/webapps/asp_fr/data/asp/publications/mc-graphics/publications/ciat/catalogue-ciat-2021---product-and-system-solutions230 V - 50 Hz 2000 2000 2,9 3000 3000 6,1 3/home/webapps/asp_fr/data/asp/publications/mc-graphics/publications/ciat/catalogue-ciat-2021---product-and-system-solutions400 V - 50 Hz 5000 5000 8,8 7500 7500 10,3 FLOWAY®VERTICAL PHE Size Nominal flow rate (m³/h) Rated current (A) Supply type 700 1000 6,2 1/home/webapps/asp_fr/data/asp/publications/mc-graphics/publications/ciat/catalogue-ciat-2021---product-and-system-solutions230 V - 50 Hz 1500 1500 4,2 3/home/webapps/asp_fr/data/asp/publications/mc-graphics/publications/ciat/catalogue-ciat-2021---product-and-system-solutions400 V - 50 Hz 2000 2000 4,2 154 154 CATALOGUE 2021