CLIMACIAT® Air handling unit General description of the CLIMACIAT ranges® ■ Casing CLIMACIAT®Airtech - Self-supporting panel construction up to size 70 - Highly-insulated panels, with thermal bridge break profiles - Double-skin panels, with 50 mm thick, long-fibre mineral wool - External walls made from sheet metal with RAL 9010 lacquer insulation, reinforced with a non-woven fibreglass fabric, coating welded on for greater vertical strength. - I nternal wall in Z275 galvanised steel - Moulded high strength bi-component polyurethane gaskets for the casing and door, guaranteeing a perfect seal. CLIMACIAT®Airclean - I nside of the AHU is perfectly smooth and even, with no - Highly-insulated panels, with thermal bridge break profiles protruding screws, as per the specifications in European standard EN 13053 (no internal handles). - External wall made from galvanised steel with RAL 9010 - Doors hung high quality frames, guaranteeing lacquer coating on durability,performance and easy access for maintenance - I nternal wallmade from galvanised steelwith RAL 9010 with adjustable hinges, external twist-lock handles and lacquer coating decompression system. - AHUs delivered in several units are equipped with specific CLIMACIAT®Airaccess factory-fitted connective pieces, which ensure perfect - Conventional double-wall panels alignment to simplify assembly. - External wall in Z275 galvanised sheet steel - Each component unit of the AHU is equipped with an 80 mm ground insulation frame and multifunction ergonomic - I nternal wall in Z275 galvanised steel supports (handling, assembly). - Each component is fitted with its own service panels. This allows independent removal for each function. The standard EN-1886, define the main construction features Thermal bridging factor [-]: The ratio between the lowest for Air Handling units. temperature difference between any point on the external Among most important features we have : surface and the mean internal air temperature and the mean ce [W.m-2.K-1]: The heat flow per area air-to-air temperature difference Thermal transmittan and temperature difference through the casing of the air CLIMACIAT®range can be upgraded from T3/TB3 to T2/TB2 handling unit. offering improved technical features and significant energy savings. OPTIONS AVAILABLE PER RANGE Airaccess Airtech Airclean Smooth RAL 9010 paintwork on external panels NA Standard Standard Smooth RAL 9010 paintwork on internal panels NA X Standard Internal and/or external panels in 304 L or Z3CN 18.10 stainless steel NA X X Internal and/or external panels in 316 L or Z3CND 17.11.02 stainless steel NA X X Stainless steel indoor baseframe X X X Sloped stainless steel indoor baseframe with drainage X X X Galvanised ground insulation frame (h = 80mm) Standard Standard Standard Painted frame NA X X Stainless steel frame NA X X Factory-assembled AHU on common rack : max size 45 X X X or maximum length 6 m Container kit X X X Adjustable support feet with 60 mm extension X X X Fixed extension feet from 200 to 400 mm X X X Sloped roof for outdoor mounting X X X Special louvers to match external casing finish X X X Protective cover for external components to match external casing finish X X X Factory-fitted cable raceway X X X Lateral technical unit X X X X: Option NA: Not applicable 162 162 CATALOGUE 2021