AQUACIATPOWER TM LD/ILD Water chiller & heat pump eleCtRiCalspeCiFiCations ■ Basic unit (excluding pump) AQUACIATPOWER TMLD 0602R0650R0750R0900R1100R1200R1350R1400R1600R1750R Power circuit supply Nominal voltage V-ph-Hz 400-3-50 Voltage range V 360-440 Control circuit supply 24 V via internal transformer Maximum operating inputpower(1) or(2) Circuit A&B kW 71,6 77,2 86,8 95,4 114,6 128,9 143,3 157,5 171,9 186,2 Power factor at maximum(1) or (2)power Standard unit power factor 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 Nominalunit current draw(4) Standard unit A 95,7 104,1 116,5 127,6 152,4 171,9 190,5 210 228,6 248,1 Maximum operating current draw (Un)(1) or (2) Standard unit A 123,9 134,4 151,0 165,2 198,4 223,1 248,0 272,7 297,6 322,3 Maximum current (Un-10%)(1) or (2) Standard unit A 132,6 143,8 161,8 176,8 212,8 239 266 292,2 319,2 345,4 Maximumstart-up current (Un)(2) + (3) Standard unit A 300 347 364 341 411 436 461 485 510 535 Unit + Electronic starter option A 257 295 312 298 359 384 409 433 458 483 AQUACIATPOWER TMLD 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R Power circuit supply Nominal voltage V-ph-Hz 400-3-50 Voltage range V 360-440 Control circuit supply 24 V via internal transformer Maximum operating input power(1)or (2) Circuit A&B kW 200,6 229,2 246,7 271,9 295,3 316,7 328,4 361,4 392,6 Power factor at maximum(1) or (2)power Standard unit power factor 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 Nominalunit current draw(4) Standard unit A 266,7 304,8 325,3 363,4 388,6 422,5 435,1 481,6 515,2 Maximum operating current draw (Un)(1)or (2) Standard unit A 347,2 396,8 432,3 478,0 517,0 556,2 575,7 634,4 686,4 Maximum current (Un-10%)(1) or (2) Standard unit A 372,4 425,6 464,8 514 556 598,2 619,2 682,4 738,4 Maximumstart-up current (Un)(2) + (3) Standard unit A 560 609 763 815 848 893 906 971 1017 Unit + Electronic starter option A 508 557 680 732 765 811 824 889 934 (1)Values at the unit's permanent maximum operating condition (as shown on the unit's nameplate). (2)Values at the unit's maximum operating condition (as shown on the unit's nameplate). (3)Maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor. (4)Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12 °C/7 °C, outdoor air temperature = 35 °C. 404 404 CATALOGUE 2021