HYDROCIATTURBO TM LWT Water chillers Heat pump Standard unit technical characteristics LWT 1400 1900 2100 2300 2600 3100 3400 3800 4200 Heating Standard unit Nominal capacity kW 649 844 939 1050 1198 1389 1538 1700 1875 Full load performances* HW1 COP kW/kW 6,13 6,26 5,93 5,79 5,89 5,76 5,97 5,89 5,67 Nominal capacity kW 629 817 915 1039 1186 1351 1491 1648 1820 HW2 COP kW/kW 4,89 4,81 4,63 4,68 4,68 4,53 4,72 4,62 4,50 Standard unit SCOP30/35°C kW/kW 7,43 7,42 7,35 7,30 7,23 6,82 6,90 6,47 6,54 Seasonal energy efficiency** HW1 ηs heat 30/35°C % 289 289 286 284 281 265 268 251 254 Prated kW 763 993 1103 1235 1409 1634 1809 2001 2203 Cooling Standard unit Nominal capacity kW 550 717 791 880 1007 1167 1302 1442 1578 Full load performances* CW1 EER net kW/kW 5,39 5,53 5,18 5,02 5,15 5,13 5,38 5,42 5,13 Eurovent class A A A B A A A A A EER gross*** 5,55 5,70 5,32 5,14 5,30 5,33 5,63 5,69 5,39 Nominal capacity kW 631 823 917 1014 1134 1348 1441 1638 1794 CW2 EER net kW/kW 8,00 8,43 7,79 7,61 7,86 7,80 8,04 8,11 7,49 Eurovent class A A A A A A A A A EER gross*** 8,41 8,88 8,19 7,94 8,25 8,37 8,68 8,78 8,17 Standard unit SEER 12/7°cComfort low temp. kW/kW 9,709,559,549,799,599,499,509,489,14 Seasonal energy efficiency** Ƞs cool 12/7°C % 385 379 379 389 381 377 377 376 363 SEPR 12/7°cProcess high temp. kWh/kWh9,4810,31 9,789,059,269,449,499,759,32 ESEER kW/kW 8,55 8,47 8,40 8,70 8,21 8,15 8,00 8,04 7,93 ESEER gross*** kW/kW 9,74 9,62 9,48 9,79 8,96 9,66 9,51 9,74 9,77 Sound levels standard unit Soundpower(1) dB(A) 89 92 94 92 94 95 94 95 97 Sound pressure at 10 m(2) dB(A) 57 60 62 60 62 63 62 63 65 Dimensions Standard unit Length mm 3140 3160 3360 4345 4345 4345 4800 4800 4800 Width mm 1270 1310 1335 1385 1385 1385 1385 1390 1410 Height mm 1780 1880 1965 2036 2036 2036 2000 2050 2100 Operatingweight(3) Standard unit kg 2402 2930 3376 4831 4855 4904 5504 6164 6730 Compressors Turbocor TT300 / TT350 Circuit A 2 2 2 1 1 1 2 2 2 Circuit B - - - 2 2 2 2 2 2 * In accordance with standard EN14511-3:2013. ** In accordance with standard EN14825:2016, average climate *** Values not Eurovent certified. Calculation without the impact of the exchanger pressure drop. HW1 Heating mode conditions: Evaporator entering/leaving water temperature 10°C/7°C, condenser entering/leaving water temperature 30°C/35°C, evaporator and condenser fouling factor 0 m. k/W2 HW2 Heating mode conditions: Evaporator entering/leaving water temperature 10°C/7°C, condenser entering/leaving water temperature 40°C/45°C, evaporator and condenser fouling factor 0 m. k/W2 CW1 Cooling mode conditions: Evaporator water entering/leaving temperature 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C, evaporator and condenser fouling factor 0 m.K/W2 CW2 Cooling mode conditions: Evaporator water entering/leaving temperature 23°C/18°C, condenser entering/leaving water temperature 30°C/35°C, evaporator and condenser fouling factor 0 m².K/W Ƞs cool 12/7 &°C SEER 12/7°C Bold values compliant to Ecodesign regulation: (EU) No 2016/2281 for Comfort application SEPR 12/7°C Bold values compliant to Ecodesign regulation: (EU) No 2016/2281 for Process application (1) in dB ref=10-12W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in accordance with ISO 9614-1 and certified by Eurovent. (2) In dB ref 20μPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information, calculated from the sound power Lw(A). (3) Values are guidelines only. Refer to the unit name plate. Eurovent certified values 564 564 CATALOGUE 2021