AQUACIATPOWER TM LD Water chillers eleCtRiCaldata Basic unit (excluding pump) AQUACIATPOWER TMLD ST 602 650 750 800 1000 1100 1250 1350 1500 Power circuit Nominal voltage V-ph-Hz 400 - 3 -50 Voltage range V 360 - 440 Control circuit supply 24 V via internal transformer Nominal unit currentdraw(1) Circuit A&B A 100 110 124 133 161 180 201 221 242 Max. operating input power(2) Circuit A&B kW 80 88 99 107 129 145 161 177 194 Unitpower factor at maximum power(2) 0,88 0,87 0,87 0,88 0,88 0,88 0,88 0,88 0,88 Maximum unit current draw (Un-10%)(3) Circuit A&B A 144 158 176 192 230 259 288 317 345 Max. current draw (Un)(4) Circuit A&B - Standard unit A 133 146 163 177 212 239 266 292 319 Circuit A&B - Unit + Power factor corrector option A 100 110 125 133 163 181 204 222 244 Maximum start-up current, standardunit (Un)(5) Circuit A&B A 307 356 374 352 423 450 476 503 529 Maximumstart-up current, unit with soft starter (Un)(5) Circuit A&B A 261 283 300 305 349 376 403 429 456 (1)Conditions equivalent to the standardised Eurovent conditions (water exchanger water inlet/outlet temperature = 12°C/7°C, outdoor air temperature = 35°C). (2)Power input, compressors + fans, at the unit operating limits (saturated suction temperature: 15 °C, saturated condensation temperature 68.3 °C) and nominal voltage of 400 V (data given on the unit's nameplate). (3)Maximum unit operating current at maximum unit power input and 360 V. (4)Maximum unit operating current at maximum unit input power and 400 V (data given on the unit's name plate). (5)Maximum instantaneous starting current at the operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of the largest compressor). Fan motor electrical data at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: current 3.8 A, starting current 20 A, input power: 1.75 kW. AQUACIATPOWER TMLD HE 602 650 750 800 1000 1100 1250 1350 1500 1600 1750 2000 Power circuit Nominal voltage V-ph-Hz 400 - 3 -50 Voltage range V 360 - 440 Control circuit supply 24 V via internal transformer Nominal unit current draw(1) Circuit A&B A 97 107 121 130 158 176 197 216 237 255 276 316 Max. operating input power(2) Circuit A&B kW 81 88 99 108 129 145 162 178 194 210 226 259 Unitpower factor at maximum power(2) 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 Unit max. operating current (Un-10%)(3) Circuit A&B A 142 154 173 189 227 255 284 312 340 369 397 454 Max. current draw (Un)(4) Circuit A&B - Standard unit A 131 142 160 174 209 235 262 287 314 340 366 419 Circuit A&B - Unit + Power factor correction option A 98 108 123 131 161 178 201 219 241 259 281 321 Maximum start-up current, standardunit (Un)(5) Circuit A&B A 305 353 371 349 420 446 472 498 525 550 577 629 Maximum start-up current, unit with softstarter (Un)(5) Circuit A&B A 259 279 297 302 346 372 399 424 451 477 503 556 (1)Conditions equivalent to the standardised Eurovent conditions (water exchanger water inlet/outlet temperature = 12°C/7°C, outdoor air temperature = 35°C). (2)Power input, compressors + fans, at the unit operating limits (saturated suction temperature: 15 °C, saturated condensation temperature: 68.3 °C) and nominal voltage of 400 V (data given on the unit's name plate). (3)Maximum unit operating current at maximum unit power input and 360 V. (4)Maximum unit operating current at maximum unit inputpower and 400 V(data given on the unit's name plate). (5)Maximum instantaneous starting current at the operating limits(maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of the largest compressor). Fan motor electrical data reported upstream of the variable speed drive at Eurovent equivalent conditions and motor ambient air temperature of 50°C at 400 V: current 3.0 A; starting current 20 A; power input: 1.75 kW. 428 428 CATALOGUE 2021