AQUACIATPOWER TM LD/ILD Water chiller & heat pump teChniCalChaRaCteRistiCs -ReveRsibleheatpUmp AQUACIATPOWER TM ILD 0602R 0700R 0800R 0900R 1000R 1150R Dimensions Standard unit Length mm 2410 2410 2410 2410 2410 3604 Width mm 2253 2253 2253 2253 2253 2253 Height mm 2324 2324 2324 2324 2324 2324 Unit + water buffer tank module option(3) Length mm 3604 3604 3604 3604 3604 4798 Operating weight(3) Standard unit kg 1569 1575 1784 1811 1817 2394 Unit + Ultra Low Noise option kg 1672 1678 1918 1946 1952 2552 Unit + Ultra LowNoise + HP dual-pump hydronic module option kg 1808 1814 2065 2092 2098 2747 Unit + Ultra Low Noise + HP dual-pump hydronic module + kg 2791 2797 3048 3075 3081 3756 Buffer tank module option Compressors Hermetic Scroll 48.3 r/s Circuit A 1 1 2 2 2 2 Circuit B 2 2 2 2 2 3 No. of power stages 3 3 4 4 4 5 Unit PED category III III III III III III Refrigerant(3) R-32 / A2L/ GWP= 675 following ARI4 kg 10,50 10,50 16,00 16,00 16,00 16,00 Circuit A tCO2e 7,1 7,1 10,8 10,8 10,8 10,8 kg 16,00 16,00 16,00 16,00 16,00 28,50 Circuit B tCO2e 10,8 10,8 10,8 10,8 10,8 19,2 Oil Circuit A l 6,6 6,6 13,2 13,2 13,2 13,2 Circuit B l 13,2 13,2 13,2 13,2 13,2 22,8 Capacity control Connect'Touch Minimum capacity % 33 33 25 25 25 20 Condenser Grooved copper tubes and aluminium fins Fans Axial with rotating impeller Standard unit Quantity 3 3 4 4 4 5 Maximum total air flow (cooling mode) l/s 11790 11790 15720 15720 15720 19650 Maximum rotation speed (heating mode) r/s 12 12 12 12 12 12 Maximum total air flow(heating mode) l/s 14460 14460 19280 19280 19280 24100 Maximum rotation speed (heating mode) r/s 16 16 16 16 16 16 Evaporator Dual-circuit plate heat exchanger Water volume l 16,2 16,2 16,2 20,7 20,7 38,7 Max. water-side operating pressure without hydronic module kPa 1000 1000 1000 1000 1000 1000 Hydraulic module (option) Pump, victaulic screen filter, relief valve, drain valve (water and air), pressure sensors Pump Centrifugal pump, monocell, 48.3 r/s, low- or high-pressure (as required), single or dual (as required) Expansion tank volume (option) l 50 50 50 50 50 80 Buffer tank volume (option) l 550 550 550 550 550 550 Max. water-side operating pressure with hydronic module kPa 400 400 400 400 400 400 Hydraulic connections with/without hydronic module Victaulic® type Connections inches 3 3 3 3 3 4 External diameter mm 88,5 88,6 88,7 88,8 88,9 114,3 Casing paint colour Colour code RAL 7035 & 7024 (3)Values are guidelines only. Refer to the unit name plate. CATALOGUE 2021 401 401