AQUACIATPOWER TM ILD Heat pump t H eChniCalChaRaCteRistiCs AQUACIATPOWER TMILD HE 602 650 800 900 9021000115012001400160018002000 Heating Standard unit Nominal capacity kW 181 198 240 216 272 294 342 359 415 474 457 436 HA1 Full load performances * COP kW/kW 3,75 3,79 3,81 3,56 3,86 3,75 3,74 3,82 3,72 3,72 3,62 3,57 Nominal capacity kW 174 191 232 245 262 282 329 345 399 456 498 537 HA2 COP kW/kW 2,99 3,05 3,04 2,91 3,11 2,96 2,98 3,04 2,95 2,97 2,95 2,94 Standard unit SCOP30/35 °C kW/kW 3,383,383,393 ,393,383,393,413,403,433,463,473,41 Seasonal energy efficiency ** HA1 ηs heat 30/35°C % 132 132133 133132132133133134135136134 Prated kW 121 134 159 169 159 194 211 231 268 305 339 356 Cooling Standard unit Nominal capacity kW 154 168 201 225 232 264 297 322 372 424 458 510 Full load performances * CA1 EER kW/kW 2,76 2,87 2,73 2,74 2,89 2,86 2,86 2,87 2,87 2,90 2,75 2,74 Eurovent class C CC CC CC CC B C C Standard unit SEER 12/7°CComfort low temp. kWh/kWh 4,07 4,08 4,09 4,13 4,16 4,21 4,16 4,23 4,32 4,33 4,30 4,22 Seasonal energy efficiency ** SEPR 12/7°CProcess high temp. kWh/kWh 5,245,29 5,29 5,16 5,13 5,39 5,52 5,45 5,56 5,64 5,40 5,18 Unit + low temperature brine SEPR Process solution option -2/-8°C kWh/kWh NA 3,55 NA 3,47 NA 3,36 3,67 NA NA NA NA NA Seasonal energy efficiency ** medium temp. *** Part Load integrated values IPLV.SI kW/kW 4,5604,6304,6704,6604,6204,6704,8404,6904,7804,8804,8504,740 Sound levels Standard unit Sound power(1) dB(A) 90 91 91 91 92 92 93 93 94 94 94 94 Sound pressure at10 m(2) dB(A) 58 59 59 59 60 60 61 61 62 62 62 62 Unit + Low Noise option Sound power(1) dB(A) 89 90 90 90 91 91 91 92 92 93 93 93 Sound pressureat 10 m(2) dB(A) 57 58 58 58 59 59 59 60 60 61 61 61 Unit + Xtra Low Noise option Sound power(1) dB(A) 84 85 86 86 86 87 87 87 88 89 89 89 Sound pressure (2)at 10m dB(A) 52 53 54 54 54 55 55 55 56 57 57 57 Unit + Super Low Noise option Sound power(1) dB(A) 82 83 84 84 84 85 85 86 86 87 87 87 Sound pressure at 10 m(2) dB(A) 50 51 52 52 52 53 53 54 54 55 55 55 Dimensions Length mm 2410 3604 4797 Width mm 2253 2253 2253 Height mm 2324 2324 2324 Unit + Buffer tank module option mm 3604 4798 5991 Operating weight (3) Standard unit kg 147915541683170521272274239626263104337033823432 Unit + Low Noise option kg 155016221775179822152400249927473239352035323612 Unit + Low Noise option + HP dual-pump hydraulic module kg 1717178519502003239526482731 301234943771 38203929 Unit + Low Noise option + HP dual-pump hydraulic module + Buffer tank kg 266427282894294633353588366739484426469947484858 module * In accordance with standard EN14511-3:2013. ** In accordance with standard EN14825:2016, average climate conditions. *** 30 % brine solution HA1 Heating mode conditions: Water heat exchanger water entering/leaving temperature 30°C/35°C, outside air temperature tdb/twb = 7°Cdb/6°C wb, evaporator fouling factor 0 m. k/W2 HA2 Heating mode conditions: Water heat exchanger water entering/leaving temperature 40°C/45°C, outside air temperature tdb/twb = 7°Cdb/6°C wb, evaporator fouling factor 0 m. k/W2 CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 12 °C/7 °C, outdoor air temperature 35 °C, evaporator fouling factor 0 m2. k/W Ƞs heat 30/35°C& SCOP 30/35°C Values in bold complywith Ecodesign Regulation (EU) No. 813/2013 for Heating applications SEER 12/7°C& SEPR 12/7°C Values calculated according to EN14825:2016 SEPR -2/-8°C Values in bold comply with Ecodesign Regulation (EU) No. 2015/1095 for Process application NA Not authorised for the specific application for the EEC market IPLV.SI Calculated as per AHRI standard 551-591 (SI). Eurovent certified values 446 446 CATALOGUE 2021