V3000 PID electronic water control, 3-point, networked KNX Radio frequency Factory-recessed remote control thermostat New generation networked control Variable flowHEE functioncontrol CIAT Wall-mounted Wall-mounted concept & design terminal with terminal with EuBac certification potentiometer display geneRaLdesCRiption The CIAT V3000 networked electronic control is designed for The V3000 control is available in a built-in version factory- use with system-powered air handling terminal units (fan coil fitted in a fan coil unit to be mounted under a sill, or a wall- units, cassettes, ductable units, etc.) in 2-tube, 4-tube, 2-tubemounted version to be connected by the installer. + 2 wire applications using recirculated air. A radio frequency remote control is available on sites which do It is available as a water controlwith actuation of 3-point not allow wiring (renovation projects etc.). 24 V valves which enable optimised control of the room temperature conditions. The V3000 control system communicates via the KNX open protocol(ISO standard 14543-3) ensuring it is completely Unlike the operation of a thermal actuator, this motor is used compatible with other products used on-site. to stabilise the valve in any state of opening (from 0 to 100 %), according to the control system requirements. desCRiption The V3000 control is a Proportional-Integral-Derivative control.The V3000 control automatically controls the CIAT HEE It controls the valve(s), the electric heater and the ventilationconcept to improve the energy performance of our fan coil speeds. It is available with display terminals or a potentiometer units: enabling the setting of the indoor comfort conditions to be optimised. - Modulating output for actuating the fan speed according to ambient requirements, The control settings (PID, deadband ventilation, etc.) are preset in the factory but can be adjusted using the room terminal withConsult our manuals for more detailed information on the display. operation and range of configuration options for this control system. Without connecting to a BMS, the V3000 can manage the master/slave function on a KNX bus (bus power supply provided as an accessory). CATALOGUE 2021 121 121