AQUACIATPOWER TM LD/ILD Water chiller & heat pump teChniCalChaRaCteRistiCs -ReveRsibleheatpUmp AQUACIATPOWER TMILD 0602R 0700R 0800R 0900R 1000R 1150R Heating Nominal capacity kW 178 197 237 256 275 317 HA1 Standard unit COP kW/kW 3,88 3,80 3,84 3,84 3,82 3,82 Full load performances* Nominal capacity kW 173 192 231 250 269 310 HA2 COP kW/kW 3,16 3,09 3,14 3,12 3,11 3,10 SCOP30/35°C kWh/kWh 3,44 3,45 3,39 3,47 3,48 3,57 Seasonal energy HA1 ηs heat % 135 135 133 136 136 140 efficiency** 30/35°C Prated kW 139 155 186 200 217 250 Unit + Rated & Seasonal high Nominal capacity kW 178 197 237 256 275 317 performance options HA1 Full load performances* COP kW/kW 3,88 3,80 3,84 3,84 3,82 3,82 SCOP30/35°C kWh/kWh 3,67 3,66 3,74 3,77 3,80 3,87 Seasonal energy HA1 ηs heat % 144 143 147 148 149 152 efficiency** 30/35°C Prated kW 138 155 185 200 216 250 Cooling Standard unit Nominal capacity kW 155 171 204 223 239 285 Full load performances* CA1 EER 2,73 2,55 2,73 2,63 2,56 2,66 Seasonal energy SEER 12/7°C Comfort low temp. kWh/kWh 4,17 4,01 4,18 4,08 4,04 4,48 efficiency** SEPR 12/7°C Process high temp. kWh/kWh 4,68 4,51 4,64 4,52 4,50 4,83 Unit + Rated & Seasonal high Nominal capacity kW 164 181 215 236 254 302 performance options CA1 Full load performances* EER kW/kW 2,87 2,72 2,86 2,80 2,76 2,85 Seasonal energy SEER 12/7°CComfort low temp. kWh/kWh 4,41 4,23 4,48 4,41 4,34 4,78 efficiency** SEPR 12/7°C Process high temp. kWh/kWh 5,47 5,23 5,41 5,23 5,15 5,49 Sound levels Unit + High temperature option/Nominal high performance Sound power(1) dB(A) 90,5 91,0 91,5 92,0 92,0 93,0 Sound pressureat 10 m (2) dB(A) 58,5 59,0 59,5 60,0 60,0 61,0 Standard unit Sound power(1) dB(A) 88,0 88,5 89,0 89,5 89,5 90,5 Sound pressure at10 m (2) dB(A) 55,5 56,0 56,5 57,0 57,0 58,0 Unit + Very Low Noise option(3) Sound power(1) dB(A) 85,0 86,0 86,5 87,0 87,0 88,0 Sound pressure at 10m (2) dB(A) 53,0 53,5 54,0 54,5 54,5 55,5 Unit + Ultra Low Noise option(3) Sound power(1) dB(A) 83,0 84,0 84,5 85,0 85,0 86,0 Sound pressureat 10 m (2) dB(A) 51,0 52,0 52,5 53,0 53,0 54,0 * In accordance with standard EN14511-3:2013. ** In accordance with EN14825:2013, average climate conditions HA1 Heating mode conditions: water type heat exchanger water inlet/outlet temperature 30 °C/35 °C, outdoor air temperature tdb/twb= 7 °C db/6 °C wb, evaporator fouling factor 0 m. k/W2 HA2 Heating mode conditions: water type heat exchanger water inlet/outlet temperature 40 °C/45 °C, outdoor air temperature tdb/twb = 7 °C db/6 °C wb, evaporator fouling factor 0 m2. k/W CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 12 °C/7 °C, outdoor air temperature 35 °C, evaporator fouling factor0 m. k/W2 Ƞs heat 30/35°C & SCOP 30/35°C Values in bold comply with Ecodesign Regulation (EU) No. 813/2013 for Heating applications SEER 12/7 °C& SEPR 12/7 °CApplicable Ecodesign regulation (EU) No. 2016/2281 (1) IndB ref=10-12W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A).Measured in accordance with ISO 9614-1 and certified by Eurovent. (2) In dB ref 20µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information, calculated from the sound power Lw(A). Eurovent certified values 400 400 CATALOGUE 2021