AQUACIATPOWER TM LD/ILD Water chiller & heat pump eleCtRiCalspeCiFiCations ■ Basic unit (excluding pump) AQUACIATPOWER TMILD 0602R0700R0800R0900R1000R1150R1250R1400R1500R1600R1750R2000R Power circuit supply Nominal voltage V-ph-Hz 400-3-50 Voltage range V 360-440 Control circuit supply 24 V via internal transformer Maximum operatinginput power(1) or (2) Circuit A&B kW 71,6 81,2 95,4 105,0114,6133,7143,3162,3171,9186,2200,6229,2 Power factor at maximum(1) or (2)power Standard unit power factor 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 Nominalunit current draw(4) Standard unit A 95,7 108,1 127,6 140 152,4178,1 190,5216,2228,6248,1 266,7304,8 Maximum operating current draw(1) o(Un) r (2) Standard unit A 129,0145,6172,0188,6205,2239,9256,5291,2307,8334,2359,1 410,4 Maximum current (Un-10%)(1) or (2) Standard unit A 135,6151,6180,8196,8212,8 250 266 303,2319,2348,4372,4425,6 Maximumstart-up current (Un)(2) + (3) Standard unit A 300 355 341 394 411 444 461 494 510 535 560 609 Unit + Electronic starter option A 257 303 298 342 359 392 409 442 458 483 508 557 (1)Values at the unit's permanent maximum operating condition (as shown on the unit's nameplate). (2)Values at the unit's maximum operating condition (as shown on the unit's nameplate). (3)Maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor. (4)Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12 °C/7 °C, outdoor air temperature = 35 °C. CATALOGUE 2021 405 405