AQUACIATPOWER TM LD/ILD Water chiller & heat pump teChniCalChaRaCteRistiCs -Coolingonly AQUACIATPOWER TM LD 0602R0650R0750R0900R1100R1200R1350R1400R1600R Dimensions Standard unit Length mm 2410 2410 2410 2410 2410 3604 3604 3604 3604 Width mm 2253 2253 2253 2253 2253 2253 2253 2253 2253 Height mm 2324 2324 2324 2324 2324 2324 2324 2324 2324 Unit + water buffer tank module option Length mm 3604 3604 3604 3604 3604 4798 4798 4798 4798 Operating weight(3) Standard unit kg 1349 1397 1397 1521 1556 1995 2049 2211 2269 Unit + Ultra Low Noise option kg 1453 1501 1501 1656 1690 2153 2208 2394 2452 Unit + Ultra Low Noise + HP dual-pump hydronic module kg 1588 1636 1636 1791 1837 2302 2403 2589 2646 option Unit + Ultra Low Noise + HP dual-pump hydronic module kg 2571 2619 2619 2774 2819 3288 3389 3575 3632 + Buffertank module option Compressors Hermetic Scroll 48.3 r/s Circuit A 1 1 1 2 2 2 2 3 3 Circuit B 2 2 2 2 2 3 3 3 3 No. of power stages 3 3 3 4 4 5 5 6 6 Unit PED category III III III III III III III III III Refrigerant(3) R-32 / A2L/ GWP= 675 following ARI4 kg 6,40 9,70 9,70 11,40 11,80 12,50 13,30 18,10 18,90 Circuit A tCO2e 4,3 6,5 6,5 7,7 8,0 8,4 9,0 12,2 12,8 kg 11,40 11,40 11,40 11,40 11,80 17,50 18,30 18,10 18,90 Circuit B tCO2e 7,7 7,7 7,7 7,7 8,0 11,8 12,4 12,2 12,8 Oil Circuit A l 6,6 6,6 6,6 13,2 13,2 13,2 13,2 19,8 19,8 Circuit B l 13,2 13,2 13,2 13,2 13,2 19,8 19,8 19,8 19,8 Capacity control Connect'Touch Minimum capacity % 33 33 25 25 25 20 20 17 17 Condenser All-aluminium micro-channel coils (MCHE) Fans Axial with rotating impeller Standard unit Quantity 3 4 4 4 4 5 5 6 6 Maximum total air flow l/s 117901572015720157201572019650196502358023580 Maximum rotation speed r/s 12 12 12 12 12 12 12 12 12 Evaporator Dual-circuit plate heat exchanger Water volume l 15 15 15 19 27 27 35 44 44 Max. water-side operating pressure without hydronic kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 module Hydraulic module (option) Pump, victaulic screen filter, relief valve, drain valve (water and air), pressure sensors Pump Centrifugal pump, monocell, 48.3 r/s, low- or high-pressure (as required), single or dual (as required) Expansion tank volume (option) l 50 50 50 50 50 80 80 80 80 Buffer tank volume (option) l 550 550 550 550 550 550 550 550 550 Max. water-side operating pressure with hydronic module kPa 400 400 400 400 400 400 400 400 400 Hydraulic connections with/without hydronic module Victaulic® type Connections inches 3 3 3 3 4 4 4 4 4 External diameter mm 88,9 88,9 88,9 88,9 114,3 114,3 114,3 114,3 114,3 Casing paint colour Colour code RAL 7035 & 7024 (1)In dB ref=10-12W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in accordance with ISO 9614-1 and certified by Eurovent. (2)In dB ref 20µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information, calculated from the sound power Lw(A). (3)Values are guidelines only. Refer to the unit name plate. CATALOGUE 2021 397 397