AQUACIATPOWER TM ILD Heat pump eleCtRiCaldata Basic unit (excluding pump) AQUACIATPOWER TMILD ST 602 650 800 900 902 1000 1150 1200 1400 1600 1800 2000 Power circuit Nominal voltage V-ph- 400 - 3 -50 Hz Voltage range V 360 - 440 Controlcircuit supply 24 V, via internal transformer Nominal unit current draw(1) Circuit A&B A 100 110 133 147 151 166 191 199 233 266 294 322 Max. operating input power(2) Circuit A&B kW 80 88 107 118 120 134 152 161 188 215 236 258 CosinePhi unit at maximum power (2) 0,88 0,87 0,87 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 Maximum unit current draw (Un-10%)(3) Circuit A&B A 144 158 192 211 215 241 273 289 337 385 422 460 Maximumunit current draw (Un)(4) Circuit A&B - Standard unit A 133 146 177 195 199 222 252 266 310 354 390 425 Circuit A&B - Unit +Power factor corrector option A 100 110 133 148 151 166 192 200 233 266 296 326 Maximumstart-up current, standard unit (Un)(5) Circuit A&B A 307 356 352 406 409 396 462 440 485 529 600 636 Maximumstart-up current, unit with soft starter (Un)(5) Circuit A&B A 261 283 305 332 336 350 389 394 438 482 527 562 (1)Conditions equivalent to the standardised Eurovent conditions (water type heat exchanger water input/output temperature = 12 °C/7 °C, outdoor air temperature = 35 °C). (2)Power input, compressors + fans, at the unit operating limits (saturated suction temperature: 15 °C, saturated condensation temperature 68.3 °C) and nominal voltage of 400 V (data given on the unit's nameplate). (3)Maximum unit operating current at maximum unit power input and 360 V. (4)Maximum unit operating current at maximum unit input power and 400 V (data given on the unit's name plate). (5)Maximum instantaneous starting current at the operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of the largest compressor). Fan motor electrical data at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: current 3.8 A, starting current 20 A, input power: 1.75 kW. AQUACIATPOWER TMILD HE H 602 650 800 900 902 1000 1150 1200 1400 1600 1800 2000 Power circuit Nominal voltage V-ph- 400 - 3 -50 Hz Voltage range V 360 - 440 Controlcircuit supply 24 V, via internal transformer Nominal unit current draw(1) Circuit A&B A 97 107 130 144 147 162 186 195 227 260 288 316 Max. operating input power(2) Circuit A&B kW 81 88 108 118 120 134 153 161 188 215 237 259 CosinePhi unit at maximum power (2) 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 Maximum unit current draw (Un-10%)(3) Circuit A&B A 142 154 189 208 211 237 268 284 331 378 416 454 Maximumunit current draw (Un)(4) Circuit A&B - Standard unit A 131 142 174 192 195 218 247 261 305 348 383 419 Circuit A&B - Unit+Power factor correction option A 98 108 131 146 148 164 188 197 230 262 291 321 Maximum start-up current, standardunit (Un)(5) Circuit A&B A 305 353 349 402 405 392 458 436 479 523 594 629 Maximumstart-up current, unit with soft starter (Un)(5) Circuit A&B A 259 279 302 329 332 346 384 389 433 476 520 556 (1)Conditions equivalent to the standardised Eurovent conditions (water type heat exchanger water input/output temperature = 12 °C/7 °C, outdoor air temperature = 35 °C). (2)Power input, compressors + fans, at the unit operating limits (saturated suction temperature: 15 °C, saturated condensation temperature: 68.3 °C) and nominal voltage of 400 V (data given on the unit's name plate). (3)Maximum unit operating current at maximum unit power input and 360 V. (4)Maximum unit operating current at maximum unit input power and 400 V (data given on the unit's name plate). (5)Maximum instantaneous starting current at the operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of the largest compressor). Fan motor electrical data reported upstream of the variable drive at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: Current 3.0 A; Starting current 20 A; Power input: 1.75 kW. 448 448 CATALOGUE 2021