COADIS LINE 600TM Comfort units COANDA effect cassette oveRview The air handling box is fitted inside the suspended ceiling at the edge of the room with the supply air opposite windows and the electrics box facing the interior of the building for models with a Visual 180° return/diffusion panel. For Visual 360° models, position the box in the centre of the room with the electrics box facing the interior of the building. Leave a minimum space of 300 mm to 600 mm at the rear of the unit to allow access to all of the air, electrical and hydraulic connections. technical The COADIS LINE must be suspended from the ceiling using access four 6 mm or 8 mm threaded rods (not supplied) to be fixed to the four unit mounting brackets with the anti-vibration resilient mounts or a nut/washer assembly positioned either side of the mounting bracket. Mounting principle 2 methods Attached using Nut/washer assembly 4 threaded rods Elastic (6mm or 8mm) damper placed either side of the mounting bracket Mounting brackets (x4) recommended Mounting system for Visual diffusers with 4 captive screws Casing position for Visual 180° diffusion only fReshaiRinLetspigot R+ pack Air quality control Fresh air control Ø 100 mm collar, max. air flow 90 m /hr recommended.3 Network balancing system (not supplied by CIAT) IAQ pack - For offices, air quality control with presence sensor (R1 pack), - For meeting rooms, air quality control with CO sensor (R+ pack).2 34 34 CATALOGUE 2021 noititrap