HYDROCIATTMLW Water chillers Heat pump Technical characteristics Standard units for high condensing temperatures LW ST + High condensing option 708 858 1008 1300 1302 1500 1508 1900 2100 2300 Heating Unit with high condens- Nominal capacity kW 328 366 413 502 536 597 618 756 845 869 ing option HW1 Full load performances* COP kW/kW 5,49 5,48 5,44 5,11 5,41 5,27 5,41 5,31 5,37 5,17 Nominal heating capacity kW 319 356 402 470 501 559 599 706 789 812 HW2 COP kW/kW 4,54 4,51 4,47 4,21 4,45 4,36 4,48 4,39 4,44 4,31 Nominal capacity kW 310 347 391 440 469 523 582 659 738 760 HW3 COP kW/kW 3,80 3,78 3,75 3,47 3,67 3,61 3,76 3,62 3,68 3,57 Unit with high condensing SCOP30/35°C kWh/kWh 5,77 5,94 5,86 5,54 5,77 5,75 5,72 5,55 5,79 5,01 option HW1 Seasonal energy efficiency** ŋs heat 30/35°C % 223 230 226 214 223 222 221 214 223 193 SCOP47/55°C kWh/kWh 4,58 4,63 4,56 4,20 4,42 4,45 4,50 4,26 4,45 3,86 HW3ŋs heat 47/55°C % 175 177 175 160 169 170 172 163 170 146 Prated kW 411 415 467 535 571 637 697 803 898 926 Cooling Unit with high condens- Nominal capacity kW 278 309 348 NA NA NA NA NA NA NA ing option CW1 Full load performances* EER kW/kW 4,83 4,80 4,76 NA NA NA NA NA NA NA Unit with high SEER 12/7°CComfort low temp. kWh/kWh 6,19 6,29 6,22 NA NA NA NA NA NA NA condensing option ŋs cool 12/7°C % 245 249 246 NA NA NA NA NA NA NA Seasonal energy efficiency** SEPR 12/7°CProcess high temp. kWh/kWh 6,67 6,72 6,57 NA NA NA NA NA NA NA Integrated Part Load Value IPLV.SI kW/kW 6,3646,5276,531 5,9286,1766,2876,1855,931 6,4335,575 Sound levels - standard unit Soundpower level(1) dB(A) 95 95 95 99 99 99 99 102 102 102 Sound pressurelevel at 1 m (2) dB(A) 78 78 78 82 82 82 82 84 84 84 Sound levels - standard unit + low noise level option Sound powerlevel(1) dB(A) 96 96 96 96 100 100 100 - - - Sound pressure levelat 1 m (2) dB(A) 78 78 78 78 82 82 82 - - - Dimensions Length mm 2724 2724 2724 2741 2741 2741 2741 3059 3059 3059 Width mm 928 928 928 936 936 936 936 1090 1090 1090 Height mm 1567 1567 1567 1692 1692 1692 1692 1858 1858 1858 Operatingweight(3) kg 2017 2036 2072 2575 2575 2613 2644 3407 3438 3462 Compressors Semi-hermetic screw compressors, 50 r/s Circuit A 1 1 1 1 1 1 1 1 1 1 Refrigerant(3) R-134a kg 84 80 78 92 92 92 92 145 135 125 Circuit A teqCO2 120 114 112 132 132 132 132 207 193 179 * In accordance with standard EN14511-3:2018. ** In accordance with standard EN14825:2016, average climate HW1 Heating mode conditions: Evaporator entering/leaving water temperature 10°C/7°C, condenser entering/leaving water temperature 30°C/35°C, evaporator and condenser fouling factor 0 m. k/W2 HW2 Heating mode conditions: Evaporator entering/leaving water temperature 10°C/7°C, condenser entering/leaving water temperature 40°C/45°C, evaporatorand condenser fouling factor 0 m. k/W2 HW3 Heating mode conditions: Evaporator entering/leaving water temperature 10°C/7°C, condenser entering/leaving water temperature 47°C/55°C, evaporator and condenser foulingfactor 0 m. k/W2 CW1 Cooling mode conditions: Evaporator water entering/leaving temperature 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C, evaporator and condenser fouling factor0 m.K/W2 Ƞs heat30/35°C& SCOP 30/35°CValues calculated in accordance with EN14825:2016 Ƞs heat47/55°C & SCOP 47/55°CValues calculated in accordance with EN14825:2016 Ƞs cool 12/7°C & SEER12/7°C Bold values compliant to Ecodesign regulation: (EU) No 2016/2281 for Comfort application SEPR 12/7°C Values calculated in accordance with EN14825:2016 IPLV.SI Calculations according to standard performances AHRI 551-591 (SI) NA Non Authorized for the specific application for CEE market (1) IndB ref=10-12W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with ISO 9614-1 and certified by Eurovent. (2) In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from the sound power level Lw(A). (3) Weight shown is guideline only. Please refer to the unit nameplate Eurovent certified values AHRI certified values 30XW-only CATALOGUE 2021 547 547