COADIS LINE 600TM Comfort units COANDA effect cassette teChniCaLChaRaCteRistiCs Coil capacity (L) COADIS LINE 600TM 612 622 622E 632 632E 624 634 2-pipe coil 0,407 0,796 0,608 1,212 1,017 Cold water coil 0,608 1,017 4-pipe coil Hot water coil 0,231 0,237 Coil coupling diameters Coil connection type: flush fit female threaded union nuts Valve outlet coupling type: "male" threaded couplings to be used COADIS LINE 600TM 612 622 624 632 634 2-pipe system G1/2" G1/2" G1/2" G1/2" G1/2" Cold water coil G1/2" G1/2" G1/2" G1/2" G1/2" 4-pipe system Hot water coil G1/2" G1/2" G1/2" G1/2" G1/2" Motor electrical data notes AC asynchronous motor HEE brushless motor COADIS LINE Motor code 612 622 - 624 632 -634 612 622 - 624 632 -634 V5 70 70 101 38 38 56 V4 45 45 77 17 17 38 Input power (W) V3 41 41 56 12 12 21 V2 38 38 47 8 8 15 V1 34 34 40 5 5 11 V5 0,30 0,30 0,32 0,18 0,18 0,40 V4 0,21 0,21 0,29 0,09 0,09 0,28 Input current (A) V3 0,19 0,19 0,24 0,07 0,07 0,17 V2 0,18 0,18 0,22 0,04 0,04 0,13 V1 0,17 0,17 0,21 0,02 0,02 0,10 Note:Specifications determined for 230V +/-10% - 50Hz supply. For operation at 60Hz, the power input and rotation speed values are generally higher. - Motor operating range: minimum return T°C: 0°C maximum return T°: 40°C Unit information plate The information plate shows all the information needed to identify the unit and its configuration. This plate is placed on the technical side that has all the connections, above the fresh air inlet. 1 Code 1 2 3 2Serial number 3Description of the unit 4Nominal motor output 5Motor rotation speed 6Coil type 7Wiring diagram reference 8Motor speed wiring 4 9 9Maximum operating pressure 10Electrical heater specifications (if fitted) 8 5 7 10 6 CATALOGUE 2021 39 39