MAGISTER® Precision air handling cabinet Options (available capacities) ■ Electric heaters CW Units CW 40 CW 53 CW 78 CW 100 Power (kW) 12 18 24 33,6 Total current (A) 17,3 26 34,7 48,6 ■ Hot water support coil Units CW40 CW53 CW78 CW100 Air flow rate (m3/h) 10 000 13 300 13 300 18 800 20 500 24 500 26 000 * Maximum operating pressure with M5 filtration 400 135 200 400 400 295 170 /ePM10 50% * Maximum operating pressure with F7 filtration 400 25 115 400 380 216 80 /ePM1: 60% Heating capacity (kW) 36 40 44 63 66 71 73 Water flow rate (m3/h) 1,5 1,7 1,9 2,7 2,8 3,1 3,1 Pressure drop (mWC) 2,2 2,6 2,8 5,3 5,8 6,6 6,9 (Coil + valve) Conditions: return air 17 °C 35% (RH) Water temperature 80/60 °C * Maximum operating pressure dependent on air flow rate. The operation point can be adjusted directly via the controller. Hence all the air flow/operating pressure combinations are possible, with the values in the table above as the maximum values. ■ Humidifier Model CW 40 to CW100 Steam flow rate (kg/h) 8 Electrical power (kW) 6 Current (A) 8,7 CATALOGUE 2021 207 207