MAGISTER® Precision air handling cabinet ■ Fitting UNDER ■ Fitting OVER Air supply via raised floor Return air on front panel Return air below Quick selection CW range - Chilled water Units CW40 CW53 CW78 CW100 Air flow rate (m3/h) 10 000 13 300 18 800 24 500 * Maximum operating pressure with M5 filtration 400 230 400 344 /ePM10 50% * Maximum operating pressure with F7 filtration 400 141 400 261 /ePM1: 60% Total/sensible cooling capacity (kW) 41.9 / 40 57.4/ 54 80.7 / 76 107 / 100 Water flow rate (m3/h) 7,2 9,8 14 18 Pressure drop (mWC) 6,4 9,6 8,1 7,1 (Coil + valve) Conditions: return air 24 °C 45% (RH) Water temperature 7/12 °C Units CW40 CW53 CW78 CW100 Air flow rate (m3/h) 13 300 13 300 20 500 27 000 * Maximum operating pressure with M5 filtration / 175 237 400 124 ePM10 50% * Maximum operating pressure with F7 filtration / 66 148 400 30 ePM1: 60% Total/sensible cooling capacity (kW) 46 / 46 51/ 51 78 / 78 100 / 100 Water flow rate (m3/h) 7,9 8,8 13 17 Pressure drop (mWC) (Coil + valve) 7,5 7,7 7,5 6,2 Conditions: return air 26 °C 40% (RH) Water temperature 10/15 °C Units CW40 CW53 CW78 CW100 Air flow rate (m3/h) 13 300 13 300 20 500 27 000 * Maximum operating pressure with M5 filtration 174 236 400 123 /ePM10 50% * Maximum operating pressure with F7 filtration 67 145 400 30 /ePM1: 60% Total/sensible cooling capacity (kW) 56 / 56 60/ 60 94 / 94 132 / 132 Water flow rate (m3/h) 9,6 10 16 23 Pressure drop (mWC) 10 10 10 10 (Coil + valve) Conditions: return air 32 °C 35% (RH) Water temperature 12/17 °C * Maximum operating pressure dependent on air flow rate. If there is a heating coil present, see "heating coil" table. The operation point can be adjusted directly via the controller. Hence all the air flow/operating pressure combinations are possible, with the values in the table above as the maximum values. 206 206 CATALOGUE 2021