AQUACIATTMLD ILD Water chillers Heat pump teChniCalChaRaCteRistiCs- Coolingonly AQUACIATTMLD 0300R 0360R 0390R 0450R 0520R 0600R Cooling Standard unit Nominal capacity kW 81,2 93,4 107 124 140 160 Full load performances* CA1 EER kW/kW 2,78 2,97 2,83 2,85 2,87 2,76 Nominal capacity kW 103 126 142 163 183 203 CA2 EER kW/kW 3,22 3,72 3,48 3,40 3,48 3,21 SEER 12/7°C Comfort low temp. kWh/kWh 4,24 4,38 4,51 4,57 4,46 4,37 Ƞs cool 12/7°C % 167 172 177 180 176 172 Seasonal energy efficiency** SEER 23/18°CComfort medium temp.kWh/kWh 5,19 5,31 5,62 5,59 5,53 5,27 SEPR 12/7°CProcess high temp. kWh/kWh 5,21 5,45 5,19 5,25 5,37 5,15 SEPR 2/-8°C Process medium temp. kWh/kWh 3,66 3,53 3,51 3,72 3,59 3,66 - Part Load integrated values IPLV.SI kW/kW 4,630 4,904 4,953 4,997 4,707 4,680 Sound levels Standard unit and High outdoor temperature option Sound power(1) dB(A) 89,0 91,5 91,5 92,0 92,0 92,0 Soundpressure at 10 m(2) dB(A) 57,5 60,0 60,0 60,5 60,5 60,5 Unit + Xtra Low Noise option Sound power(1) dB(A) 80,0 83,0 83,0 83,0 83,0 83,0 Sound pressure at 10 m(2) dB(A) 48,5 51,5 51,5 51,5 51,5 51,5 Dimensions Length mm 1061 2258 2258 2258 2258 2258 Width mm 2050 2050 2050 2050 2050 2050 Height mm 1330 1330 1330 1330 1330 1330 Unit height (XtraFan option) mm 1341 1341 1341 1341 1341 1341 Unit height (optional buffer tank) mm 1930 1930 1930 1930 1930 1930 Unit height (XtraFan + buffer tank option) mm 1972 1972 1972 1972 1972 1972 Operating weight with micro-channel coils(3) Standard unit kg 447 665 725 733 848 863 Unit + High-pressure single-pump option kg 467 684 745 758 874 888 Unit + High-pressure dual-pump option kg 494 711 772 791 906 921 Unit + high-pressure single-pump and buffer tank options kg 819 1102 1163 1176 1292 1306 Unit + high-pressure dual-pump and buffer tank options kg 846 1129 1190 1209 1324 1339 * In accordance with standard EN14511-3:2018. ** In accordance with standard EN14825:2013, average climate CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 12 °C/7 °C, outdoor air temperature 35 °C, evaporator fouling factor 0 m2. k/W CA2 Cooling mode conditions: evaporator water inlet/outlet temperature 23 °C/18 °C, outdoor air temperature 35 °C, evaporator fouling factor 0 m2. k/W Ƞs cool12/7°C & SEER 12/7°CValues in bold comply with Ecodesign Regulation (EU) No. 2016/2281 for Comfort applications SEER 23/18 °C Values in bold comply with Ecodesign Regulation (EU) No. 2016/2281 for Comfort applications SEPR-2/-8 °C Values in bold comply with Applicable Ecodesign regulation: (EU) No 2015/1095 for Process applications IPLV.SI Calculated as per standard AHRI 551-591 (1) IndB ref=10-12W, (A) weighting. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). Measured in accordance with ISO 9614-1. (2) In dB ref 20 µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). For information, calculated from the sound power level Lw(A). (3) Values are guidelines only. Refer to the unit name plate. Eurovent certified values 350 350 CATALOGUE 2021