AQUACIATTMLD ILD Water chillers Heat pump teChniCalChaRaCteRistiCs- Coolingonly AQUACIATTMLD 150 180 200 240 260 300 360 390 450 520 600 Cooling Standard unit CA1 Nominal capacity kW 40 44 51 58 69 79 89 97 115 138 156 Full load performances* EER kW/kW 2,89 2,78 2,69 2,68 2,84 2,71 2,85 2,74 2,68 2,82 2,66 CA2EERNominal capacity kW 53 59 69 81 85 99 115 127 152 172 196 kW/kW 3,47 3,34 3,14 3,34 2,98 3,08 3,19 3,11 3,12 3,01 3,03 Standard unit SEER 12/7°CComfort low kWh/kWh 3,904,07 4,12 4,003,833,91 4,21 4,204,10 3,95 4,19 Seasonal energy efficiency** temp. ηs co 12/7°Col % 153 160 162 157 150 154 165 165 161 155 164 SEPR 12/7°C Process high kWh/kWh 5,325,355,285,125,125,18 5,165,155,525,10 5,33 temp. Unit with low-temperature SEPR 8°C Process brine solution option -2/- kWh/kWh 2,883,21 2,91 3,093,042,752,973,123,10 3,073,02 Seasonal energy efficiency** medium temp. Part Loadintegrated values IPLV.SI kW/kW 4,510 4,6804,7804,5604,2504,3805,5404,5304,5304,2804,620 Sound levels Standard unit Sound power (1) dB(A) 80 81 81 81 87 87 84 84 84 90 90 Sound pressureat 10 m(2) dB(A) 49 49 49 49 55 55 52 52 52 58 58 Unit + Xtra Low Noise option Sound power (1) dB(A) 79 80 80 80 80 80 83 83 83 83 83 Sound pressureat 10 m(2) dB(A) 48 48 48 48 48 48 51 51 51 51 51 Dimensions Length mm 1090 1090 1090 1090 1090 1090 2270 2270 2270 2270 2270 Width mm 2109 2109 2109 2109 2109 2109 2123 2123 2123 2123 2123 Height mm 1330 1330 1330 1330 1330 1330 1330 1330 1330 1330 1330 Height with Buffer Tank Module mm 1930 1930 1930 1930 1930 1930 1930 1930 1930 1930 1930 Operatingweight with micro-channel coils(3) Standard unit kg 422 430 436 449 445 463 753 762 771 829 854 Unit + High pressure single pump option kg 463 472 478 491 487 505 820 829 842 903 928 Unit + High pressure dual pump option kg 489 498 504 517 513 531 865 874 891 940 965 Unit + high pressure single pump + Water buffer tank module option kg 859 868 874 887 883 901 1253 1262 1275 1336 1361 Unit + high pressure dual-pump + Water buffer tank module option kg 885 894 900 913 909 927 1298 1307 1324 1373 1398 Compressors Hermetic Scroll 48.3 r/s Circuit A Qty 2 2 2 2 2 2 3 3 3 2 2 Circuit B Qty - - - - - - - - - 2 2 No. of power stages Qty 2 2 2 2 2 2 3 3 3 4 4 Refrigerant with micro-channel coils(3) R410A GWP=2088 following ARI4 Circuit A kg 4,7 5,3 5,9 6,7 6,2 7,3 10,7 10,8 11,4 6,5 7,4 tCO2e 9,8 11,1 12,3 14,0 12,9 15,2 22,3 22,6 23,8 13,6 15,5 Circuit B kg - - - - - - - - - 6,5 7,4 tCO2e - - - - - - - - - 13,6 15,5 * In accordance with standard EN14511-3:2013. ** In accordance with standard EN14825:2016, average climate CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 12 °C/7 °C, outdoor air temperature 35 °C, evaporator fouling factor0 m. k/W2 CA2 Cooling mode conditions: evaporator water inlet/outlet temperature 23 °C/18 °C, outdoor air temperature 35 °C, evaporator fouling factor0 m. k/W2 ŋs cool12/7°C& SEER 12/7°C Values in bold comply with Ecodesign Regulation (EU) No. 2016/2281 for Comfort application SEPR 12/7°C Values in bold comply with Ecodesign Regulation (EU) No. 2016/2281 for Process application SEPR -2/-8°C Values in bold comply with Ecodesign Regulation (EU) No. 2015/1095 for Process application IPLV.SI Calculated as per AHRI standard 551-591 (SI). - Not applicable (1) indB ref=10-12 W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). Measured in accordance with ISO 9614-1. (2) In dB ref 20 µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). For information, calculated from the sound power level Lw(A). (3) Values are guidelines only. Refer to the unit name plate. Eurovent certified values 362 362 CATALOGUE 2021