POWERCIATTM LX Water chillers teChniCalspeCiFiCations POWERCIATTMLX XE 0808 0908 1008 1108 1358 1528 1858 2008 2158 2308 2528 2628 3028 Power circuit supply Nominal voltage V-ph-Hz 400-3-50 Voltage range V 360-440 Control circuit supply 24 V via internal transformer Maximum operating inputpower(1) Standard unit kW 126 137 147 172 192 210 257 278 308 327 357 375 440 Unit + Xtra / Super Low Noise option kW 124 135 145 170 189 208 254 274 304 323 353 371 434 Power factor at maximumpower(2) Displacement Power Factor (Cos Phi)+ 0,90 0,89 0,89 0,90 0,89 0,89 0,90 0,90 0,89 0,89 0,89 0,88 0,89 Displacement Power Factor (Cos Phi) unit + Xtra / 0,90 0,89 0,89 0,90 0,89 0,89 0,90 0,90 0,89 0,89 0,89 0,88 0,89 Super Low noise option Nominaloperating current draw(3) Circuit(a)1 A 145 161 177 203 234 255 315 339 390 411 427 483 521 Unit + Xtra / Super Low Noise option A 142 158 174 199 230 251 310 333 384 405 420 476 512 Maximumoperating current draw (Un)(1) Circuit(a)1 A 203 221 239 277 310 340 414 447 502 532 578 617 715 Unit + Xtra / Super Low Noise option A 200 218 236 273 306 336 409 441 496 526 571 610 706 Maximum current (Un-10 %)(2) Circuit(a)1 A 215 234 253 293 328 360 438 473 532 564 613 655 759 Unit + Xtra / Super Low Noise option A 212 231 250 289 324 356 433 467 526 558 606 648 750 Start-up current(3) + (4) Circuit(a)1 A 181 174 190 314 408 408 408 432 626 632 632 660 652 Unit + Xtra / SuperLow Noise option A 179 172 188 312 405 406 405 428 622 628 628 656 646 Maximum start-up current (Un)(2) + (3) Circuit(a)1 A 210 221 221 343 439 439 487 486 671 686 686 727 749 Unit + Xtra / Super Low Noise option A 208 219 219 341 436 437 484 482 667 682 682 723 743 (1)Values at the unit's permanent maximum operating condition (as shown on the unit's nameplate). (2)Values at the unit's maximum operating condition (as shown on the unit's nameplate). (3)Maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor. (4)Standardised EUROVENT conditions, water-cooled exchanger inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C. (a)When the machines are equipped with two power supplies, circuit 1 is intended to supply refrigerant circuit A and circuit 2 supplies refrigerant circuit B. For units LX 3428 to 4608: circuit 1 supplies circuit A, circuit 2 supplies circuit B. 474 474 CATALOGUE 2021